Large operating temperature rnage: -20..+60 degrees Celsius
Compact DIN rail housing: 93 x 78 x 56
Standards-conformal for both office and industrial environments:
Increased noise immunity for industrial areas
Stricter noise emission for residential and commercial areas
Background information: W&T Interfaces or Com-Servers are frequently used with a 24V power supply in large numbers at a central location. In such cases a common supply for the interfaces makes the application significantly clearer than would be the case when powering the devices with individual dedicated power supplies.
If there is no high-capacity 24V power supply in the installation, this task can be elegantly and cost-effectively solved using the #11076 60W DIN rail mounted power supply, with which multiple Interfaces or Com-Servers can be powered centrally.
The power supply can of course also be used where in addition to the 24V supply for the W&T Interface you also need power for the rest of the installation. In this case you simply need to ensure that the power consumed does not exceed the rated power of the DIN rail power supply.
Thanks to the generous operating temperature range, the DIN rail mount power supply is also ideal for applications where the standard plug-in power supply provided with the Interfaces cannot be used due to the expected high ambient temperatures.
Technical data:
Output power:
max. 60W
Efficiency:
typ. 84%
Input voltage:
100..240VAC
Frequency:
47..63 Hz
Input current:
0.8A at 230V AC
Inrush:
max. 36A at 230V AC
Leakage current:
<1mA at 230V AC
Output voltage:
24V DC (adjustable 21.6..26.4V)
Tolerance:
+/-1%
Ripple:
max. 150mV
Rated current:
2.5A
Minimum load:
none
Overcurrent limiter:
at 105%...160% of the nominal current
Short circuit protected:
Yes
Overvoltage protection:
Shutdown at 115%..135% of nominal voltage Reset using POWER ON
Meets EN 55022 B EN 61000-3-2, EN 61000-3-3 EN 61000-4-2, EN 61000-4-3 EN 61000-4-4, EN 61000-4-5 EN 61000-4-6, EN 61000-4-8 EN 61000-4-11, ENV 50204 EN 61204-3, EN 61000-6-2