These compact devices include everything you need to connect digital input and output ports of industrial 24V technology to the network. In many cases, it is even possible to manage without additional relays. The wide input voltage range also enables operation at 12 V.
Like the configuration of the device, the reading and/or control of the input/output ports is done via a Web browser. Beyond this, access facilities via TCP/UDP sockets, OPC, SNMP or via e-mail are also available.
Possible applications:
Remote control, industrial control and automation, home and building monitoring and control technology, process visualization, door monitoring, gate control, factory data collection, machine data collection, expansion for PLC’s, fire alarm systems, fault reporting systems and much more.
Technical data:
Network:
10 / 100BaseT autosensing
Protocol:
TCP and UDP sockets, client and server
SNMP including traps
SMTP e-mail sending
OPC server
Inventory keeping, group management
Response times:
Data and switching traffic: typically 12 ms
Digital outputs:
1 group of 12 x digital outputs 6V - 30V, 500mA
Grouping of 2 or 4 outputs
Maximum group current 2 A
Maximum total current 6 A
Short-circuit-protected
Digital inputs:
12 x digital inputs,
Max. input voltage +/-30 V
Protected against polarity reversal within this range
Switching threshold 8V +/- 1V
"On" current = 2.2 mA
Connections:
2 x 16 screw-type terminals
Galvanic isolation:
Digital outputs - network: min. 1000 V
Digital inputs - network: min. 2000 V
Digital inputs - outputs: min. 1000 V
Serial port:
RS232 interface as an optional configuration access.