These compact devices include everything you need to connect digital input and output ports of industrial 24V technology to the network. In many cases, it is even possible to manage without additional relays. The wide input voltage range also enables operation at 12 V.
Like the configuration of the device, the reading and/or control of the input/output ports is done via a Web browser. Beyond this, access facilities via TCP/UDP sockets, OPC, SNMP or via e-mail are also available.
Possible applications:
Remote control, traffic engineering, traffic light control, vehicle counting, signal control, tunnel monitoring, light control, controlling loudspeaker announcements, fire alarm systems, fault reporting equipment and much more.
Technical data:
Network:
10/100BaseT autosensing
Protocol:
TCP and UDP sockets, client and server
SNMP including traps
SMTP e-mail sending
OPC server
Inventory keeping, group management
Response times:
Data and switching traffic: Typically 12ms
Digital outputs:
1 group of 24 x digital outputs 6V - 30V, 500mA
Grouping of 2 or 4 outputs
Max. group current 2 A
Max. total current 6 A
Short-circuit-protected
Digital inputs:
24 x digital inputs,
Max. input voltage +/-30 V
Protected against polarity reversal within this range
Switching threshold 8V +/- 1V
"On" current = 2.2 mA
Adapters:
VG96 connector
Galvanic isolation:
Digital outputs - network: Min. 1000 V
Digital inputs - network: min. 2000 V
Digital inputs - outputs: Min. 1000 V
Serial port:
RS232 interface as an optional configuration access.
Displays:
Status LEDs for network
48 LEDs for digital statuses
Operating elements:
1 hidden reset button
Power supply:
24V DC +/- 10% Current draw with no load approx. 100mA
Storage temperature:
-25°C - 70°C
Operating temperature:
0°C - 60°C
Form factor:
OEM plug-in module for 19’’ realization Aluminum front panel 10 TE (50.80 mm)