Data sheet:
Web-Thermograph
Article no.: 57605
This article has been replaced by the expanded successor model Web Thermometer Pt100 / Pt1000 respectively.
Monitor and graphically display temperatures
Example application: http://klima.wut.de
Properties
General information
- Graphic display of the stored temperature values
- Interactive display, user-scalable
- Display of limit violations
- Freely selectable line color
- Monitor temperatures and curves with your browser
- HTML page design user-variable
- Direct access to current temperature value, e.g., for integration into other Web pages
- SNMP temperature polling /Alarm traps for incorporating into your existing SNMP management system
- E-mail for alarm or reporting functions
- Adapters:
- 10/100MBit
- NTC probe included, PT100 probe can be connected
- Easy Start:
- Connect sensor and network cable
- Connect supply voltage
- Assign IP number
- That’s it!
- Application examples:
- Monitor temperatures in the server room, network cabinet or office
- Direct display of multiple measuring points in the browser via Java applet
- Send alarms when limits are exceeded via e-mail, SNMP trap, TCP client, Syslog
- Logging of the measured values via FTP, Excel file, e-mail attachment, internal memory
Technical data
- Temperature sensors:
- NTC and PT100 connection
- Network:
- 10/100BaseT autosensing
- Supply voltage:
- 12-24V AC / DC using screw terminal
Measuring unit- Sensor:
- NTC 10k, PT100-connection, 2-,3- or 4-wire
- Measuring range:
- -45°C...105°C (PT100)
- -45°C...75°C (NTC)
- Resolution:
- 1/10°C
- Measuring error:
- ±0.3°C, ±5% (NTC) ±0.3°C, ±2% (PT100)
- Polling frequency:
- 1, 5, 15, 60 min
- Memory depth (64k):
- min. 14 weeks, max. 16 years
- Deviation of the internal clock:
- max. 4.32 min. / month
Other data- Electrical isolation:
- Signal inputs to network: min. 500 volts
- E-mail function:
- Mail for sending alarms or as reporting function
- Supply voltage:
- DC 12V (-5%) - 34V (+5%)
- AC 9Veff (-5%) - 24Veff (+5%)
- DC 48V (+10%) on request
- Current consumption:
- AVG: 200mA @12VDC, 100mA @24VDC, 100mA @20VAC
- Max: 240mA @12VDC
- Configuration interface:
- RS232 serial port, 9600 baud, 8 data bits, 1 stop bit, no parity
- Housing:
- Plastic compact housing, 105x75x22mm
- Weight:
- approx. 200g
- Ambient storage temperature:
- -40..+70°C
- Ambient operating temperature:
- 0 .. +60°C
- Scope of delivery:
- 1x Web-Thermograph for top-hat rail mount
- 1x NTC thermocouple
Please order power supplies separately as accessories