Data sheet:
Web-IO 4.0 Analog 0-20mA
Measure, tunnel, output analog signals...
The combined solution for analog in- or output signals brings your measurements into the network and back to the terminal. Use the Web-IO Analog-In/Out to measure analog signals, tunnel them over the network and output them again as analog signals at a remote location.
Properties
Analog connection:
Two channels, selectably configurable as:
- Current input:
- Input signal: 0/4..20mA active/passive
- Current output:
- Output signal: 0/4..20mA
- Current input:
Connectivity:
- Intuitive Web interface for simpler configuration
- Monitor analog measurements and processes from a browser
- Alarm and reporting function:
- E-mail for alarm or reporting functions
- SNMP polling / alarm traps
- Configure up to 12 alarm messages
- Box2Box mode tunnels analog signals between two devices
- Set analog values via socket command or direct entry
- Active current input 0/4-20mA
- Interactive display, custom scalable
- Dynamic integration into other Web sites:
- Direct access to current measurement values, e.g. JavaScript (AJAX).
- Current Industry 4.0 protocols:
- OPC UA, REST and MQTT support
- Additional software interfaces for incorporating into your systems/databases:
- SNMPv1, SNMPv2c, SNMPv3
- OPC UA, OPC DA
- Syslog
- Sensobase (database integration via ODBC)
- TCP and UDP sockets, client and server
- FTP (data logging)
- Modbus TCP
- Possible applications:
- Connect each sensor with 0/4..20mA output and monitor measurements
- Control analog actuators over the network
- Network as extension: tunnel analog values via Box2Box mode
- Logging of measurements via FTP, Excel file, email attachment and internal memory
Data logger:
- Internal data logger
- Memory capacity: min. 150 days, max. 99 years
- Save frequency: 15, 30 sec, 1, 5, 15, 60 min
- Document measurement data online in the W&T Cloud and access from anywhere in the world
- Internal clock
- Time synchronization via time server calibration
- Battery-backed device clock
Standards & more
- Supply voltage via Power-over-Ethernet (PoE)
- Phantom power using data pairs
- Power over unused wire pairs
- External power supply is an alternative
- Conforms to standards both in office and industrial environments:
- High noise resistance per EN 61000-6-2
- Low noise emission per EN 55032:2015 + A1 Cl. B, EN 61000-3-2 & EN 61000-3-3
- 5 year guarantee
Technical data
Connections and displays:
- Current input passive:
- 0/4..20mA, 100Ohm
- Current input active:
- 0/4..20mA, burden max. 500 Ohms, active voltage Umax 14V / 40mA
- Current output:
- 0/4..20mA, burden max. 500 Ohms, supply 10V guaranteed
- Analog in-/output:
- 8-pin terminal block
- Conductor cross-section 0.2-1.3mm²
- Stripped length 6-8mm
- Current loop monitoring:
- Short circuit protected and open-loop detection
- Network:
- 10/100BaseT autosensing
- RJ45
- IPv6 on request
- Galvanic isolation:
- Measurement inputs to network: min. 1500 volts
- Power supply:
- Power-over-Ethernet (PoE) or
- DC 12V .. 48V (+/-10%)
- Current consumption:
- PoE Class 1 (0.44 - 3.84W)
- typ. 100mA @ 24V DC with external supply
- Displays:
- 1 LED power
- 2 LEDs network status
- 4 LEDs status and error
Measuring unit:
- Resolution:
- Current input: 2.5µA
- Measuring error:
- max. 0.5% FSR (Full Scale Range 0..20mA) TA = 0-60°C
- Storage frequency:
- 15, 30 sec., 1, 5, 15, 60 min
- Storage depth:
- min. 150 days, max. 99 years
- Measurement value acquisition (can be polled over the network and can generate alarms if desired):
- 2 / second
Housing and other data:
- Housing:
- Plastic compact housing for top-hat rail mount
- 105x22x75mm (LxWxH)
- Enclosure rating:
- IP20
- Weight:
- approx. 140 g
- Ambient storage temperature:
- -40..+70°C
- Ambient operating temperature:
- 0 .. +60°C
- Scope of delivery:
- 1x Web-IO Analog-In/Out 2x 0..20mA PoE
- for DIN rail mount
- 1x Quick Guide in German/English
* Our offering is intended only for commercial users. We will be happy to refer private end customers to trading partners through whom our products can be purchased.